C Series Heat Exchanger Section 8 - Cooling System - Group 08 Page 8-45 Use clean low-pressure water to backflush the heat exchanger. Connect the hose to the heat exchanger sea water outlet to allow the water to backflush the system. This will remove and flush away any loose debris. Make sure the end cavities are cleared of all debris. Inspect each plug. If either plug has eroded over 50 percent, it must be replaced. NOTE: Do not use thread sealant on the zinc plugs. They must be grounded to the component to function properly. Install the zinc plugs in the aftercooler and heat exchanger. Refer to Procedure 008-059 (Zinc Anode). Install the sea water inlet and outlet connections.
Torque Value: 5 N•m [ 44 in-lb ] Erosion Limits New A = Approximately 19 mm [0.75 in] 51 mm [2 in] B = Approximately 6.4 mm [0.25 in] 16 mm [0.63 in]