C Series Generator, Main Section 21 - Main Power Generator - Group 21 Page 21-9 1. Page Button - Cyclic selection of the display mode 7. Indicator Light - On = no alarm 8. Indicator Light - Flashing = generator failure, Steady (MEASUREMENT>ADJUSTMENT>HISTORY) 2. Horn Reset Button - Deactivates the Horn 3. Mode - Cyclic backward selection of the generator set On = Alarm still active, Off = No alarm active. 9. Fault Reset Button - Acknowledges faults and alarms 10. Enter Button - Confirm set-point value 11. Select the set-point, select the screen, or decrease operation mode (AUT>MAN>OFF) 4. Mode - Cyclic forward selection of the generator set operation mode (OFF>MAN>AUT) 5.
Start Button - Starts the generator set 6. Stop Button - Stops the generator set the set-point value 12. Select the screen or select set-point The following is a guide to the menus and operation of the push buttons: To select the generator set mode, use button 3 or 4 to select the requested generator set operation mode (OFF - MAN - AUT). Display Menus - There are two display menus available: MEASUREMENT and ADJUSTMENT. Each menu consists of several screens. Press button 1 repeatedly to select the requested menu. To view measured data: Use button 1 repeatedly to select the MEASUREMENT menu. Use buttons 1 and 7 to select the screen with the requested data. To view and edit set points: 1.
Press button 2 repeatedly to select the adjustment menu 2. Use button 11 and 12 to select the requested set-points group 3. Press button 8 to confirm 4. Use buttons 11 and 12 to select requested set-points 5. Set points marked with an asterisk are password protected 6. Press button 10 to edit 7. Use buttons 11 and 12 to modify the set-point. When buttons 11 or 12 are pressed for two seconds, auto repeat function is activated 8. Press button 10 to confirm or button 1 to leave without change 9. Press button 1 to leave selected set-points group. To change the display contrast: Press button 10 and either button 11 or 12 at the same time to adjust for the best display contrast.
OFF mode - No start of the generator set is possible. Outputs STARTER and FUEL SOLENOID are not energized. No reaction if buttons START or STOP are pressed. Function Description: STOP - stops the generator set. MAN mode - START - starts the generator set. Hints - The engine can run without load unlimited time. The controller does not automatically stop the running generator set in MAN mode. The controller does not start the generator set when binary input REM START/STOP is closed Start-stop sequence (simplified).
MODE = MAN (Engine start/stop request is given by pressing buttons START and STOP) MODE = AUT (Engine start/stop request is given by binary input REM START/STOP) State Condition of Transition Action Next State Ready Start request PRESTART on Prestart time counter started Prestart RPM greater than 2 or oil pressure greater than starting prestart oil Stop (Stop failure) OFF mode selected or shutdown alarm active Not Ready Not Ready RPM less than 2, oil pressure less than starting prestart oil, no shutdown alarm active, other than OFF mode selected Ready Prestart Prestart time elapsed STARTER on, FUEL SOLENOID on, Maximum Crank time counter started Cranking