Generator, Main C Series Page 21-10 Section 21 - Main Power Generator - Group 21 Hint - Threshold level for D+ input is 80 percent supply voltage. AUT mode - The controller does not respond to buttons START or STOP. Engine start/stop request is given by binary input REM START/STOP. Un-Classed Remote Panel - The un-classed remote panel consists of one maintained action, two part, illuminated push-button switch. The two part, illuminated push-button has a snap-action switching function and serves to start and stop the generator engine. See Figure 4. Figure 4, Un-Classed Remote Panel.
State Condition of Transition Action Next State Cranking RPM greater than Start RPM STARTER off, PRESTART off Starting D+ input activated or oil pressure detected or Generator voltage greater than 25% voltage nominal STARTER off, PRESTART off Cranking Maximum Crank time elapsed, first attempt STARTER off, FUEL SOLENOID off, STOP SOLENOID on Crank Failure pause timer started Crank pause Max Crank time elapsed, last attempt STARTER off, PRESTART off Shutdown (Start failure) Crank pause Crank Fail pause elapsed STARTER on, FUEL SOLENOID on, STOP SOLENOID off, Maximum Crank time counter started Cranking Starting 80% Nominal speed reached READY TO LOAD on Minimum, Maximum Stabilizer Time counter started Running RPM 0 or an other shutdown condition FUEL SOLENOID off, STOP SOLENOID on Shutdown 60 second Elapsed FUEL SOLENOID off, STOP SOLENOID on Shutdown (Start failure) Running Stop request READY TO LOAD off, Cooling time timer started Cooling RPM equal to 0 or any other shutdown condition FUEL SOLENOID off, STOP SOLENOID on Shutdown Cooling Cooling time elapsed FUEL SOLENOID off, STOP SOLENOID on Stop RPM equal to 0 or any other shutdown condition FUEL SOLENOID off, STOP SOLENOID on Shutdown Start request READY TO LOAD on Running Stop RPM equal to 0, Oil pressure less than Starting PRESTART Oil Ready 60 second Elapsed Stop (Stop failure)