Peripheral Devices The Suspect Parameter Number options for the output configuration are the same as those for the input configuration. There are several options for the Trigger Condition parameter but the simplest to use is the “Condition Exists – Specific Event” selection. Following is an example of configuring the module for use with a switch on one of the inputs:
Input Configuration Event Input Function #1 Active State Configuration Event Input Function #1 Event Notification Delay Time Event Input Function #1 Suspect Parameter Number “Custom Event” Event Input Function #1 Failure Mode Identifier “Condition Exists” Output Configuration Event Output Function #1 Suspect Parameter Number “Custom Event #1” Event Output Function #1 Trigger Condition “Condition Exists – Specific Event” Ten seconds after the switch on Input #1 closes, the relay contacts on Output #1 change states.
17.3.2.2 Configuring the Discrete I/O Module for J1939 Data Link Messages The Discrete I/O Modules can be configured a number of different ways to take action on specific diagnostic, warning, or shutdown messages that are broadcast on the J1939 data link. Messages placed on the J1939 data link that can apply to industrial applications are the diagnostic, warning, and/or shutdown messages concerning coolant temperature, coolant level, fuel pressure, fuel temperature (C11 ACERT-C32 ACERT), oil pressure, intake manifold temperature, and battery voltage. Usually, the best way to configure the module is the simplest.
For example, if it is desired to activate a relay output when the engine low oil pressure warning is broadcast by the engine ECU, then the following selections for each of the parameters would produce the desired outcome: Event Output Function #1 Suspect Parameter Number Engine Oil Pressure Event Output Function #1 Trigger Condition Low Warning – Specific Event For a high coolant temperature warning, the configuration should look like:
Event Output Function #2 Suspect Parameter Number Engine Coolant Temperature Event Output Function #2 Trigger Condition High Warning – Specific Event In the second example, the output would be triggered only if the ECU transmits a high coolant temperature warning on the J1939 data link. If the Trigger Condition was programmed to “High Warning – General Event,” the output would have been triggered when either the high coolant temperature warning or the high coolant temperature shutdown messages are transmitted by the engine ECU. If “Warning – General Event” is selected for the Trigger Condition, any warning transmitted by the ECU will trigger the output. Note:
If an output is programmed to trigger when an engine shutdown message is transmitted by the engine ECU, the output will remain latched until the engine ECU sends a reset message over the J1939. If an output is programmed to trigger when an input is configured for shutdown, the output will remain latched until the shutdown condition is removed and the Discrete I/O module is power cycled. Note: In order for the engine ECU to transmit a warning or shutdown message over the J1939 data link, the corresponding engine monitoring configuration parameter in the engine ECU must be programmed to I N D U S T R I A L E N G I N E E L E C T R O N I C S 120