Caterpillar C7 ACERT, C9 ACERT, C11 ACERT, C13 ACERT, C15 ACERT, C18 ACERT, C27 ACERT, C32 ACERT — Caterpillar C7 ACERT, C9 ACERT, C11 ACERT, C13 ACERT, C15 ACERT, C18 ACERT, C27 ACERT, C32 ACERT User Manual

Peripheral Devices The 8 Form C relay outputs are rated for resistive loads of 3A at 30VDC for Normally Closed (NC) or Normally Open (NO) relays, 2A at 125VAC for Normally Closed (NC) or Normally Open (NO) relays, and 2A at 277VAC for Normally Closed (NC) or Normally Open (NO) relays. Inductive load ratings for the outputs are 0.5A at 250VAC cos ı = 0.4, 1.0A at 250VAC cos ı = 0.8, and 0.8A at 250VAC cos ı = 0.9. Figure 5 is a representation of an output of the discrete I/O module. Figure 5 Figure 6 shows the 40-pin connector layout for the inputs, outputs, and ground pins. The Caterpillar part number for the 40-pin mating connector is 9X-7147.

Figure 6 I N D U S T R I A L E N G I N E E L E C T R O N I C S 122