Starting and Stopping the Engine 9.2 Air Shutoff System 9.2.1 Air Shutoff System Operation The air shutoff system works in conjunction with the engine overspeed feature. If equipped, an air shutoff system that is controlled by the engine ECU can stop the engine when the engine speed reaches a customer programmed set point. The overspeed verify switch input is available for the customer to test the system at 75 percent of the engine speed configured as the overspeed limit in the engine monitoring system. When the engine speed exceeds the engine overspeed shutdown value configured in the engine monitoring system, fuel injection will be disabled and the air shutoff solenoid will be activated.

Once the air shutoff solenoid is activated, then the key switch (switched power) must be cycled and the air shutoff doors must be manually reset in order to re-start the engine. The air shutoff doors will remain closed until the ECU power has been cycled and the doors have been manually reset. An additional switch may be added to the circuit to provide a manual air shutoff option. Refer to the circuit diagram in 9.2.3. A momentary switch is recommended since many relays are not rated for continuous duty and may be damaged if the switch stays closed for an extended period of time. Using this switch to shut the damper does not cause the ECU to log an event. NOTE:

Refer to Engine Monitoring and Protection (section 15) for information about the overspeed verify switch. 9.2.2 Air Shutoff System Configuration One parameter must be configured in Cat ET prior to using air shutoff. In the configuration screen, air shutoff defaults to “disabled” and must be set to “enabled.” Engine monitoring system parameter for engine overspeed may be changed to establish the level of protection necessary for the specific installation. Refer to the engine overspeed section in Engine Monitoring and Protection (section 15). 9.2.3 Air Shutoff System Installation Contact the Application Support Center for availability of the air shutoff system hardware.

Caterpillar does not offer this hardware on all engine sizes. NOTE: Source current from the ECU is 2 amps under normal operating conditions. However, under cold operating conditions, the ECU may source as low as 1.0 amp to the relay. Positive Battery 15 A Momentary Manual Air Inlet Shutoff Switch (Optional) Air Shutoff Solenoid Air Shutoff Relay P1/J1 ECU Negative Battery Overspeed Verify Switch Negative Battery I N D U S T R I A L E N G I N E E L E C T R O N I C S 50 11 67 54 Inlet Air Shutoff Solenoid Relay Solenoid Common Overspeed Verify Switch