Engine Monitoring and Protection 15.1.3.2 Engine Speed Monitoring Configuration Two parameters can be configured in Cat ET to customize the monitoring system for engine overspeed monitoring. 1. ECU action for an event code defaults to “On” for Warning and Shutdown. All actions can be configured to “On” or “Off.” 2. Engine speed maximum limit default is specific to the engine model and is defined in the configuration table below. The maximum speed limit for warning and shutdown can be lowered within the range specified in the configuration table below. The time delay is defined by the factory and cannot be modified.
The following table summarizes the configuration default settings and configuration ranges for engine overspeed monitoring: 15.1.3.3 Engine Speed Monitoring Installation No installation is required for engine speed monitoring to function. 15.1.4 Inlet Air Temperature 15.1.4.1 Inlet Air Temperature Monitoring Operation Inlet air temperature is monitored to automatically protect the engine from exceeding a maximum inlet air temperature limit. The inlet air temperature measured by the ECU is compared to a maximum inlet air temperature limit configured in the monitoring system for inlet air temperature monitoring.
The maximum inlet air temperature is checked for each ECU action level configured in the monitoring system. If the inlet air temperature is above the maximum inlet air temperature for the specified action level delay time, then the ECU takes the appropriate action to respond to the fault condition. Once the fault is detected, the ECU illuminates the warning and diagnostic lamps and logs the appropriate event code from the following table for the action taken:
A P P L I C A T I O N A N D I N S T A L L A T I O N G U I D E 97 ENGINE OVERSPEED MONITORING CONFIGURATION Action Default Value Time Delay (sec) Set Points Range Default Range Default Warning On None 1.0 C7 ACERT/C9 ACERT 1800 to 2600 C11 ACERT-C15 ACERT 1800 to 2600 C18 ACERT 1800 to 2500 C27 ACERT/C32 ACERT 1800 to 2600 C7 ACERT/C9 ACERT 2600 C11 ACERT-C15 ACERT 2600 C18 ACERT 2500 C27 ACERT/C32 ACERT 2600 Shutdown On None 1.0 C7 ACERT/C9 ACERT 1800 to 2800 C11 ACERT-C15 ACERT 1800 to 2800 C18 ACERT 1800 to 2700 C27 ACERT/C32 ACERT 800 to 2800 C7 ACERT/C9 ACERT 2800 C11 ACERT-C15 ACERT 2800 C18 ACERT 2700 C27 ACERT/C32 ACERT 2800 Cat ET Description J1939 Description Status SPN FMI High Inlet Air Temperature Air Inlet Temperature Warning 172 15 High Inlet Air Temperature Air Inlet Temperature Derate 172 16