Deutz — 5.1.4 ANALYSIS OF LIFT AND ASM ALARMS

5. ALARMS 5.1 LIFT AND ASM CONTROL UNIT ALARMS 5.1.4 ANALYSIS OF LIFT AND ASM ALARMS Extended alarm: 12 Supply Pos. Sens. Standard alarm: 26 DESCRIPTION The control unit detects that the power input to the lift position sensor is not correct. CHECK Check that the contacts on connector “POS SEN” and on those of the lift control unit, “JX1” and “JX2”, are firmly at- tached and not oxidised. With the starter key in the “I” (ON) position, check that the power input to the lift position sensor is correct (5 V approx measured between pin 3 (positive) and pin 1 (negative) of connector “POS SEN”).

With the starter key in the “O” (OFF) position, connect a test meter to pin 3 of connector “POS SEN” and to chassis earth, and measure the resistance to ensure there are no short circuits to earth (meter reading: infinity). With the starter key in the “O” (OFF) position, connect a test meter to pin 2 of connector “POS SEN” and to chassis earth, and measure the resistance to ensure there are no short circuits to earth (meter reading: infinity). With the starter key in the “I” (ON) position, connect a test meter to pin 2 of connector “POS SEN” and to chassis earth, and check to ensure there are no short circuits to positive (meter reading: 0V).

Clear all alarms, turn the starter key first to “O” (OFF) and then back to the “I” (ON) position again, and if the alarm is still present, the control unit must be renewed.. 20-50 0.012.8732.4 5 4 15 23 21 20 4 5 20 21 15 23 JX1 GND4 J2 TKAB2 5 2 F34 7.5A +15 0441.9533 21 2223 1 2 3 POS. SENS. U S 0.012.8672.4 D0017551 4 5 20 21 1 5 23 GND4 5 2 2 1 2 22 3 1 2 3 U S