SERDIA WHAT TO DO IF...? 8.2 EMR1 8.2.1 ENGINE SURGES Fault finding: Troubleshooting with the EMR1 is done in the same way as for engines with mechanical regulators, i.e. the engine com- ponents and functions such as pump, control rod movement, fuel supply, etc, are examined. In most cases, especially if the engine was running correctly before engine surges begin to occur, the fault does not lie in the EMR1. Controller setting: Controller setting is performed mainly for new operation modes, and should be thoroughly tested and documented with the system (engine and installation) in all operating conditions.
If the new application is connected and enabled, the user-specific controller parameters must be confirmed with company headquarters. Follower engines with the same operation mode do not usually require any additional adjustments. Opening the menus : SERDIA main menu -> Tasks menu -> Governor setting -> Execute General rules for setting correction: Setting correction is carried out with the engine running. Raising the P/I/D parts increases the control tolerance range. Enter the value to be corrected in the "new value“ field. One way of doing this is •select the old value with the mouse, then simply type in the new value (the old value is deleted automatically).
Click on the "PC->ECU" button to send the new value to the control unit. The governor applies the new setting, and the result will be detectable in the engine behaviour. After setting correction has been carried out successfully and before disconnecting the voltage supply (circuit 15), the new parameters must be stored in the EMR1. To do this, click on the "Save in ECU" button. 20-305