Komatsu — A3 OPNEMEN A3 OPNEMEN E- 1 Abnormality in governor, pump controller power source ( controller LED is OFF)

TROUBLESHOOTING E-1 E-1 Abnormality in governor, pump controller power source (controller LED is OFF) # This troubleshooting is carried out when there is still an abnormality, so when disconnecting the connector and inserting the T-adapter, or when removing the T-adapter and returning the connector to its original position, if the service code E is not displayed, the problem has been removed. # Check that fuse 1 is not blown. # Before carrying out troubleshooting, check that all the related connectors are properly inserted. # Always connect any disconnected connectors before going on to the next step. # When the starting motor rotates correctly.

(If the starting motor also does not rotate, go to E-8) E-1 Related electric circuit diagram 20-116 YES 1 Is voltage between C01 (7) (13) and C02 (11) (21) normal? 2 YES Is voltage between • Turn starting switch fuse 1 and chassis ON. NO normal? • 20 - 30 V • Turn starting switch NO ON. • 20 - 30 V Cause Remedy Defective governor, pump controller Defective contact, or disconnection in wiring harness between fuse 1 and C01 (female) (7) (13) Defective contact, or disconnection in wiring harness between fuse 1- H15 (2)-M14 (2) (1)-battery relay M Replace Repair or replace Repair or replace