Komatsu — H- 25 Swing speed is faster than specified swing speed

TESTING AND ADJUSTING ACTION TAKEN BY MONITOR PANEL WHEN ABNORMALITY OCCURS AND PROBLEMS IN MACHINE 20-237 Condition when normal (voltage, current, resistance) Action by controller when abnormality is detected Problem that appears on machine when there is abnormality • When starting switch is turned ON, keep time switch pressed for 5 seconds to actuate clear function. - 1. Service code cannot be cleared. 2. Time becomes 00:00 - 1. Service code cannot be cleared 2. Time becomes 00:00 3. Clock does not advance. • Voltage between P01 (7) - chassis Buzzer ON: Max. 1V Buzzer OFF: 20-30V # When there is disconnection, E103 is not displayed and buzzer does not sound. - Buzzer does not sound.

• Resistance between P11 (male) and P12 (female): Max. 1 Ω (start engine) - If detection of abnormality continues, air cleaner clogging caution lamp flashes and buzzer sounds. • Resistance between sensor terminal and chassis: Max. 1 Ω (engine running at mid-range speed). - If detection of abnormality continues, engine oil pressure caution lamp flashes and buzzer sounds. • Resistance between P07 (1) and (2): Min. 3.156 kΩ (start engine). - 1. If detection of abnormality contin- ues, coolant temperature caution lamp flashes and buzzer sounds. 2. If detection of abnormality contin- ues, engine speed is set to low idling.