Cab Heater and Air Conditioner, Valeo 83.00 Troubleshooting Recirculation Door Actuator Circuit Tests Test Conditions Test Point Good Result What to Do if Test Fails actuator position sensor feedback signal circuit key on, engine off Backprobe pins A11 and B5 at control head connector. 0.8V (recirc. on) to 4.7V (recirc. off) Check wiring between control head and recirculation door actuator. all connectors connected If wiring is okay, replace the actuator. * The voltage should be approximately the same as the battery voltage. It is assumed that reference voltage and ground circuits are functioning.
Table 5, Recirculation Door Actuator Circuit Tests Blower Motor Circuit Tests 1000 rpm to reduce the load on the motor and a comparison is made between the sensor reading and the maximum limit. If the tempera- ture is still too high, the blower speed is further reduced to the minimum value of approxi- mately 500 rpm and a temperature comparison is made to the maximum. If, after the second comparison, the temperature is still too high, the motor will shut down until it has cooled sufficiently. The blower motor power and ground are supplied directly to the blower motor assembly. The blower speed is controlled by the fan switch on the control head (climate control panel).
The control head sends a pulse width modulated (PWM) signal to the blower motor. The frequency of this signal is 2000 Hz. The pulse width varies with the fan switch selection. The protection modes for the blower motor are as follows: Perform the tests in Table 6 in the sequence pre- sented. The directions under the column "What to Do if Test Fails" are sometimes dependent on good re- sults from previous tests. If any of the tests fail, stop and perform the specified repair or check. If the blower motor passes the tests in Table 6 and the blower still does not operate properly, check the blower motor.
To quickly check for normal operation, set the fan switch to high and listen for a change in the sound of the blower near the HVAC unit while pressing the recirculation button on and off. The blower will be louder when recirculation is enabled. Reverse Voltage Protection—The motor will not operate if the polarity of the motor leads, cir- cuits 98F and ground, are reversed. Current Protection—If the motor exceeds the maximum limit, the speed will be reduced until the current is within the limits (23.5A maxi- mum).
Temperature Protection—If the motor’s internal temperature sensor senses that the tempera- ture is too high, the blower speed is reduced to Blower Motor Circuit Tests Test Conditions Test Point Good Result What to Do if Test Fails main power to blower motor battery switch on (if equipped) Measure between pin 4 of blower motor connector and negative battery post. 12V * Check fuse F2 in the PDM under the hood. If the fuse is blown, check for shorted wiring or a damaged blower motor. key off blower motor connector removed Check for an open in circuit 98F. Business Class M2 Workshop Manual, Supplement 13, March 2008 300/12