Cab Heater and Air Conditioner, Valeo 83.00 Troubleshooting Blower Motor Circuit Tests Test Conditions Test Point Good Result What to Do if Test Fails blower motor ground circuit battery switch on (if equipped) Measure between pin 3 of blower motor connector and the positive battery post. 12V * Check for an open in blower motor ground circuit. key off blower motor connector removed PWM signal from control head battery switch on (if equipped) key on, engine off Probe pins 4 and 5 of the blower motor connector, harness side (DMM set to measure frequency). 0 Hz fan off Check circuit 338H. Check control head.

blower motor connector disconnected 0 Hz fan on high change the fan (blower) speed setting on the control head and observe frequency using the digital multimeter (DMM) 2000 Hz all other speeds voltage drop (power circuit) battery switch on (if equipped) Backprobe pin 4 at the blower motor connector, other lead on positive battery post. less than 0.5V Locate high resistance or open in circuit 98F. key on, engine off all connectors connected fan (blower) speed on high voltage drop (ground circuit) battery switch on (if equipped) Backprobe pin 3 at the blower motor connector, other lead on negative battery post. less than 0.5V Locate high resistance or open in blower motor ground circuit.

key on, engine off all connectors connected fan (blower) speed on high blower motor current draw battery switch on (if equipped) Use current clamp around circuit 98F or blower motor ground wire. less than 23.5A Check blower motor. key on, engine off all connectors connected * The voltage should be approximately the same as the battery voltage. Table 6, Blower Motor Circuit Tests fan (blower) speed on high Evaporator Probe Circuit Tests poor cooling will result. The control head will shut off the compressor when the evaporator temperature is near the point where freezing may occur.

See Table 7 for evaporator probe temperature versus re- sistance values for units manufactured up to and in- cluding January 7, 2007. See Table 8 for evaporator probe temperature versus resistance values for units manufactured on or after January 8, 2007. The evaporator temperature sensor is a resistive ele- ment, where the resistance increases as the tem- perature decreases. The control head (climate con- trol panel) uses this sensor to determine the evaporator temperature. The control head uses the temperature information to determine if the A/C com- pressor should be engaged or not in order to prevent the evaporator core from freezing.

As refrigerant flows through the evaporator, condensation will form on the surface of the evaporator. If this condensation freezes because the evaporator temperature is too low, airflow will be restricted through the core and Perform the tests in Table 9 in the sequence pre- sented. The directions under the column "What to Do if Test Fails" are sometimes dependent on good re- sults from previous tests. If any of the tests fail, stop and perform the specified repair or check. Business Class M2 Workshop Manual, Supplement 13, March 2008 300/13