48 Pre-Commissioning QA Inspection EP COMMISSIONING & SUPPORT SERVICES (800) 789-9774 Customer Service (562) 463-7192 Fax Server Date iMACs PROJECT #: Project Name Stock Order ID #: Purchase Order #: 0 Package Serial #: 0 EQUIPMENT TYPE: Generator 0 0 0 ( Yes, No, Not Applicable, Need Assistance) Exhaust system COMPLETED?
Installation design prevents exhaust recirculation Flexible connection to engine Support prevents load on turbocharger/manifold Installation allows for pipework expansion Pipework / muffler supported at required intervals Joints welded or flanges secure with correct gaskets Stack/tail pipe prevents rain/snow ingress Flues are not combined in stack Condensate drain provided Exit directed away from buildings / personnel System is lagged & clad as required Building penetration & weathering complete & sealed Flammable materials properly protected Fill point installed & alarm fitted Storage facility secure 0 Ventilation & Attenuation Air intake is at least 150% area of air outlet Design prevents hot air recirculation & rain ingress Design accounts for prevailing wind Air flow direction is from alternator to radiator Radiator outlet is ducted to attenuator / louver Attenuator / louvers complete & sealed to building Louver mechanisms complete & wired as required Electrical bonding completed Forced ventilation provided for remote cooled sets Bird guard is fitted to intake & outlet 0 Electrical system Control system Field wiring to set mounted control complete Customer wiring to set mounted control complete Interconnection to remote control complete Emergency stop controls wired Set / Switchgear / Changeover / Transfer Means of disconnection / isolation provided Switchgear installation & pre-testing completed Cables installed correctly, marked, allow movement Power connections complete & torque-marked Cable tests complete & certificates available Electrical general All electrical boxes clean & covers replaced Auxiliary electrical supply complete Grounding system complete & tested Electrical bonding of services / assemblies complete Utility supply available as required Small power & lighting circuits tested & certificated