hitachi — PREPARATION FOR PERFORMANCE TESTS

TROUBLESHOOTING / Troubleshooting A MC FAULT CODE 11910, 11911, 11914, 11918, 11920, 11983, 11984 (CAN HARNESS CHECK) Check the wiring connections first. Disconnect all connectors of MC, ICF, ECM and monitor unit. Check for continuity between ground circuit (MC, ICF, ECM, monitor unit) and CAN circuit. YES Open circuit in CAN harness between ground circuit and CAN circuit. YES · Key switch: OFF · Refer to “Discontinuity Check between CAN Circuit and Power Circuit” on T5-6-65 to 68. · Key switch: OFF · Refer to “Discontinuity Check between CAN Circuit and Ground Circuit” on T5-6-61 to 64. · Key switch: OFF · Refer to “Continuity Check in CAN Harness” on T5-6-58. Retry by using Dr. ZX.

Check if fault code 11004-2 is displayed. Open circuit in CAN harness between MC and monitor unit. NO Normal. NO T5-6-81 Check for continuity between power circuit (MC, ICF, NO ECM, monitor unit) and CAN circuit. Check for continuity in CAN harness between YES MC and monitor unit.