John Deere 450DLC — Main Controller (MCF) Circuit Theory of Operation

TM2361 (24JUN08) 9015-15-28 450DLC Excavator Operation and Tests 062608 PN=472 Sub-System Diagnostics The ECM receives signals from the boost temperature • Auto-idle switch (S8) (OFF) sensor, engine coolant temperature sensor, and • Pilot shutoff switch (S3) (lever in LOCK position) engine intake air temperature sensor. The ECM then • Hydraulic oil temperature sensor (B40) sends this information through the CAN data link to the • Pump 1 control pressure sensor (B36) MCF. • Pump 2 control pressure sensor (B38) The MCF compares the information from the ECM with MCF outputs involved:

signals it receives from hydraulic oil temperature sensor (B40) (terminal D2), engine speed dial (R15) • Pump 1 control solenoid (Y12) (terminal D15), and A/C controller (A7) (terminal C8). • Pump 2 control solenoid (Y13) When A/C controller (A7) is OFF, no ground is When the pump learning switch (S18) is moved to the available to the MCF at terminal C8. When the MCF PUMP LEARNING position (opposite E), ground is does not detect a ground at terminal C8, it sends an provided to terminal B11 on the MCF.

When the MCF appropriate amount of current to fan pump control detects ground at terminal B11 and all the conditions solenoid (Y14) to vary the fan speed as engine stated below are met, the MCF cycles the pump temperature and conditions require. control solenoids (Y12 and Y13) while monitoring the current to the solenoids. NOTE: Increasing current to the fan pump control solenoid causes the pump displacement At the same time, the MCF monitors pump swash (swash plate angle) to decrease. plate angle by sensing signals from pump control 9015 15 28 pressure sensors (B36 and B38).

The MCF compares When A/C controller (A7) is ON, a ground is sent to the current used to drive the solenoids with the signal the MCF at terminal C8. When the MCF detects this from the pressure sensors. It then calculates for any ground, the fan operates similar to when the A/C differences and makes adjustments as needed. controller is OFF, but the threshold speed of the fan is slightly increased. The pump learning control requires the following conditions: For hydraulic fan drive system operation, see Fan Drive System Diagram and Operation.

(Group • Engine running at fast idle 9025-05.) • Hydraulic oil temperature at 50 ± 5°C (122 ± 41°F • Auto-idle switch OFF For operation of fan pump, see Fan Drive Pump • HP mode enabled Regulator Operation. (Group 9025-05.) • Pilot shutoff lever at rearward (LOCK) position • Hydraulic control levers in neutral position Pump Learning Control: The pump learning procedure must be performed anytime the pump, pump regulator, Attachment Mode Control: The attachment mode or pump control solenoid valve have been replaced. control limits the maximum flow rate of pump 2 and The Dr.ZX diagnostic application is needed to perform controls the appropriate flow rate for the attachment.

the pump learning procedure. See Dr.ZX Diagnostic Application. (Group 9015-20.) MCF inputs involved: MCF inputs involved: • Attachment pressure sensor (B45) • Monitor controller (through CAN) (attachment mode • Pump learning switch (S18) selected) • Engine control dial (R15) • Pump 1 delivery pressure sensor (B35) • Power mode switch (S12) (HP position) • Pump 1 control pressure sensor (B36) Continued on next page CS33148,00008EB –19–28APR06–11/15