General Specifications 10 CONTROL CHARACTERISTICS Control Method Pulse Width Modulated (PWM) Control Mode 1: V / F (V / F control), 2: SVC (Sensorless Vector Control), 3: PMSVC Starting Torque Reach up to 150% or above at 0.5Hz. V / F Curve 4 point adjustable V / F curve and square curve Speed Response Ability 5 Hz Torque Limit Light Duty: Max. 130% torque current; Normal Duty: Max. 160% torque current Torque Accuracy ± 5% Max. Output Frequency 599.00 Hz Frequency Output Accuracy Digital command: ± 0.01%, -10ºC ~ +40 ºC; Analog command: ±0.1%, 25ºC ±10ºC Output Frequency Resolution Digital command: 0.01 Hz; Analog command: Max.

output frequency x 0.03 / 60 Hz (± 11-bit) Overload Tolerance Normal duty: 120% of rated current can endure for1 minute during every 5 minutes 160% of rated current can endure for 3 seconds during every 30 seconds Light duty: 120% of rated current can endure for1 minute Frequency Setting Signal 0 ~ +10 V, 4 ~ 20 mA, 0 ~ 20 mA, pulse input Accel. / decel.

Time 0.00 ~ 600.00 / 0.0 ~ 6000.0 seconds Main Control Function Momentary power loss ride thru, Speed search, Over-torque detection, Torque limit, 16-step speed (max), Accel/decel time switch, S-curve accel/ decel, 3-wire sequence, Auto-Tuning (rotational, stationary), Dwell, Slip compensation, Torque compensation, JOG frequency, Frequency upper/lower limit settings, DC injection braking at start/stop, High slip braking, PID control (with sleep function),Energy saving control, MODOBUS communication (RS- 485 RJ45, max.

5.2 Kbps) Fan Control VFD300FP4E and above are PWM control VFD220FP4E and below are on / off switch control PROTECTION CHARACTERISTICS Motor Protection Electronic thermal relay protection Over-Current Protection Light duty: Over-current protection for 200% rated current, Normal duty: Over-current protection for 240% rated current, Current clamp (Light duty: 130 ~ 135%) (Normal duty:

170 ~ 175%) Over-Voltage Protection Drive will stop when DC-BUS voltage exceeds 820 V Over-Temperature Protection Built-in temperature sensor Stall Prevention Stall prevention during acceleration, deceleration and running independently Restart After Instantaneous Power Failure Parameter setting up to 20 seconds Grounding Leakage Current Protection Leakage current is higher than 50% of rated current of the AC motor drive Short-circuit Current Rating (SCCR) Per UL508C, the drive is suitable for use on a circuit capable of delivering not more than 100 kA symmetrical amperes (rms) when protected by fuses given in the fuse table International Certifications , , GB/T12668-2