Specifications * 1 A zero phase reactor is required to fulfill EMC category C1 NOTE • The value of the carrier frequency is a factory setting. To increase the carrier frequency, the current needs to be decreased. Please see derating curve diagram of Pr. 06-55 for more information. • When a load is a surge load, use a higher level model.
9 Frame Size A B C D0 D Models VFD- FP4E- ____ __ 007 015 022 037 040 055 075 110 150 185 220 300 370 450 550 750 900 OUTPUT RATING LIGHT DUTY Rated Output Capacity (kVA) 2.4 3.3 4.4 6.8 8.4 10.4 14.3 19 25 30 36 48 58 73 88 120 143 Rated Output Current (A) 3 4.2 5.5 8.5 10.5 13 18 24 32 38 45 60 73 91 110 150 180 Applicable Motor Output ( kW) 0.75 1.5 2.2 3.7 4.0 5.5 7.5 11 15 18.5 22 30 37 45 55 75 90 Applicable Motor Output (HP) 1 2 3 5 5 7.5 10 15 20 25 30 40 50 60 75 100 125 Overload Tolerance 120% for 60 seconds in every 5 minutes Max.
Output Frequency (Hz) 599 Carrier Frequency (kHz) 2 ~ 15 (default 6) 2 ~ 10 (default 6) 2 ~ 9 (default 6) NORMAL DUTY Rated Output Capacity (kVA) 1.4 2.4 3.2 4.8 7.2 8.4 10 14 19 25 30 36 48 58 73 88 120 Rated Output Current (A) 1.7 3.0 4.0 6.0 9.0 10.5 12 18 24 32 38 45 60 73 91 110 150 Applicable Motor Output ( kW) 0.4 0.75 1.5 2.2 3.7 4.0 5.5 7.5 11 15 18.5 22 30 37 45 55 75 Applicable Motor Output (HP) 0.5 1 2 3 5 5 7.5 10 15 20 25 30 40 53 60 75 100 Overload Tolerance 120% for 60 seconds in every 5 minutes 160% for 3 seconds in every 25 seconds Max.
Output Frequency (Hz) 599 Carrier Frequency (kHz) 2 ~ 15 (default 6) 2 ~ 10 (default 6) 2 ~ 9 (default 6) INPUT RATING Input Current (A) Light Duty 3.0 4.2 5.5 8.5 10.5 13 18 24 32 38 45 60 73 91 110 150 180 Input Current (A) Normal Duty 1.7 3.0 4.0 6.0 9.0 10.5 12 18 24 32 38 45 60 73 91 110 150 Rated Voltage / Frequency 3-phase AC 380 V ~ 480 V (-15% ~ +10%), 50 / 60 Hz Operating Voltage Range 323 ~ 528 V AC Frequency Tolerance 47 ~ 63 Hz Efcfi iency (%) 97 Power factor > 0.98 Drive Weight (Kg) 6.8 14.5 26.5 42 59.5 Cooling Method Natural cooling Fan cooling Braking Chopper Frame A, B, C, Built-in DC Choke Built-in DC choke meets EN6100-3-12 EMC Filter Built-in EMC filter meets EN61800-3 C2 & C1*1