Environment for Operation, Storage and Transportation Specifications for Operation Temperature and Protection Level *Note: 15єC ~ 50єC, without derating; 51єC ~ 60єC, with derating 8 DO NOT expose the AC motor drive to harsh environments, such as dust, direct sunlight, corrosive / inflammable gasses, humidity, liquid or vibrations. The salts in the air must be less than 0.01 mg / cm2 every year. Ambient Conditions Installation Location IEC60364-1 / IEC60664-1 Pollution degree 2, indoor use only Surrounding Temperature (ºC) Storage / Transportation -25 ~ 70 Only allowed at non-condensation, non-frost, non-conductive environment Rated Humidity Operation Max. 95% Storage / Transportation Max.
95% Only allowed at non-condensation, non-frost, non-conductive environment Air Pressure (kPa) Operation / Storage 86 ~ 106 Transportation 70 ~ 106 Environment IEC60721-3-3 Operation Class 3C3; Class 3S2 Storage Class 1C2; Class 1S2 Transportation Class 2C2; Class 2S2 Altitude Operation If the AC motor drive is installed at an altitude 0 ~ 1,000 m, follow normal operation restrictions. For every 100 m increase in altitude, the AC motor drive needs to either lower rated current by 1% or by 0.5 ºC of temperature for operation.If the drive is installed at an altitude above 2,000 m, please refer to the voltage derating graph in the user manual for more instructions Note:
Voltage derating is not needed for a Center Ground System, and maximum installation altitude is 4,000m. Vibration Operating IEC 60068-2-6 Frame A: 2Hz ≦ f ≦ 13.2Hz / Amplitude 1mm; 13.2Hz Shock Operating IEC 60068-2-27 Frame A; B; C; D0: Max. 30 G; 11 ms; Frame D: Max. 15 G; 11 ms In protective shipping package Vibration IEC 60068-2-64 10 Hz ≦ f ≦ 100 Hz / ASD: 1.0m2/s3; 100 Hz ≦ f ≦ 200 Hz / Slope: -3dB/octave Shock Cardboard box type: Free fall drop in accordance with ISTA 1A Wooden box type: In accordance with ISTA 1E (4 side incline) and ISTA 2B (Bottom side drop) Operation Position Max.
allowed ofsf et angle ±10 º (under normal installation position) 10 10 Model Frame Protection Level OperationTemperature VFDxxxFPxxx-52 Frame A ~ D: 0.75 ~ 90 kW IP55/NEMA12 -10 °C ~ 50 °C* VFDxxxFPxxx-41 Frame A ~ D: 0.75 ~ 90 kW IP41/NEMA1 -10 °C ~ 50 °C*