7. Connection Procedure 7.3.3. Creating the I/O Table Create the I/O table for the PLC. 16 1 If the operating mode of the PLC is RUN Mode or Monitor Mode, change it to Program Mode, by following steps (1) to (3). (1)Select Operating Mode - Program from the PLC Menu of the CX-Programmer. (2)The dialog box on the right is displayed. Check the message on the dialog and if there is no problem, click the Yes Button. *Refer to Additional Information in 7.3.2. Starting the CX-Programmer and Connecting Online with the PLC for the settings concerning the dialog display. (3)Confirm that Stop/Program Mode is displayed on the right of the PLC model in the project workspace of the CX-Programmer.
2 Select Edit - I/O Table and Unit Setup from the PLC Menu of the CX-Programmer. The PLC IO Table Window is displayed.