General Specifications 12 Control Characteristics Control Method Pulse Width Modulated (PWM) Control Mode 1: V / F (V / F control), 2: SVC (Sensorless Vector Control), 3: PM (Permanent Magnet Motor) Starting Torque Reach up to 150% or above at 0.5 Hz V / F Curve 4 point adjustable V / F curve and square curve Speed Response Ability 5 Hz Torque Limit Light Duty: Max. 130% torque current; Normal Duty: Max. 160% torque current Torque Accuracy ±5% Max. Output Frequency (Hz) 230 V model: 599.00 (55 kW and above: 400.00) 460 V model: 599.00 (90 kW and above: 400.00) 575 V / 690 V model: 599.00 Frequency Output Accuracy Digital command: ±0.01%, -10 °C ~ +40 °C, Analog command:

±0.1%, 25 ±10 °C Output Frequency Resolution Digital command: 0.01 Hz; Analog command: Max. output frequency x 0.03 / 60 Hz (±11 bit) Overload Tolerance Light duty: 120% of rated current for 1 minute during every 5 minutes Normal duty: 120% of rated current for 1 minute during every 5 minutes; 160% of rated current for 3 seconds during every 25 seconds Frequency Setting Signal 0 ~ +10 V, 4 ~ 20 mA, 0 ~ 20 mA Accel. / decel. Time 0.00 ~ 600.00 / 0.0 ~ 6000.0 seconds Main Control Function Fault restart Torque limit High-Slip braking Dwell 3-wire sequence Speed search Parameter copy JOG frequency Slip compensation Torque compensation S-curve accel / dece l Energy saving control Accel / Decel.

Time switch Frequency upper / lower limit settings Momentary power loss ride thru PID control (with sleep function) Auto-Tuning (rotational, stationary) DC injection braking at start / stop BACnet Communication 17-step speed (max.) Over-torque detectio n Modbus communication (RS-485 RJ45, Max. 5.2 Kbps) Fan Control 230 V model: Model with spec higher than VFD185CP23 (included) are PWM control; Model with spec lower than VFD150CP23 (not included) are on / off switch control. 460 V model: Model with spec higher than VFD220CP43/4E (included) are PWM control; Model with spec lower than VFD185CP43/4E (not included) are on / off switch control. 575 V / 690 V model:

PWM control Protection Characteristics Motor Protection Electronic thermal relay protection Over-Current Protection 230 V / 460 V model: Light duty: Over-current protection for 185% rated current, Normal duty: Over-current protection for 240% rated current, Current clamp (Light duty: 130 ~ 135%);(Normal duty: 170 ~ 175%) 575 V / 690 V model: Over-current protection for 225% rated current Current clamp (Light duty: around 128 ~ 141%);(Normal duty: around 170 ~ 175%) Over-Voltage Protection 230 V model: drive will stop when DC bus voltage exceeds 410 V 460 V model: drive will stop when DC bus voltage exceeds 820 V 575V model: drive will stop when DC bus voltage exceeds 1016 V 690 V model:

drive will stop when DC bus voltage exceeds 1189 V Over-Temperature Protection built-in temperature sensor Stall Prevention Stall prevention during acceleration, deceleration and running indepenently Restart After Instantaneous Power Failure Parameter setting up to 20 seconds Grounding Leakage Current Protection Leakage current is higher than 50% of rated current of the AC motor drive Short-circuit Current Rating (SCCR) Per UL508C, the drive is suitable for use on a circuit capable of delivering not more than 100kA symmetrical amperes (rms) when protected by fuses given in the fuse table International Certifications* SEMI F47, GB/T12668.3 Note : 1.

EAC Certification is for 230 V and 460 V models only 2. No UL certification for models above 500 kW