omron — Using PID Control

Simplicity on the Worksite Solutions Guide for FAQs: E5CC/E5EC Using PID Control Executing Autotuning Turn ON the power supply. 1 Operating Display Adjustment Level ← l.adj (L.ADJ) will be displayed to show that the Adjustment Level has been entered. The four numeric digits that identify the product code are displayed. Press the (Level) Key for less than 1 second. Change the parameter with the Key . 2 Adjustment Level ← at (AT): Indicates the Autotuning parameter. ← Default setting is off (OFF): Autotuning stopped. Press the (Mode ) Key several times to display at (AT). Use the (Up and Down) Keys to select at-2 (AT-2) (100% autotuning).

Autotuning will start at at-2 3 Using PID Control Adjustment Level ← The TUNE indicator will light during autotuning. off (OFF) at-2 (At-2) at-1 (At-1) : Autotuning stopped (default). : 100% autotuning executed. : Refer to page 3-6. ← at-2 (AT-2): 100% autotuning executed. 4 When the indicator goes out, autotuning is finished. Adjustment Level ← When the TUNE indicator goes out, autotuning is finished. (When finished, press the (Level) Key to return to the operation display.) *You can return to the Operation Level during autotuning execution. ← After Returning to Operation Level Operating Display ← flashing: Autotuning is being executed.

3-4 Simplicity on the Worksite Solutions Guide for FAQs: E5CC/E5EC