Digital Temperature Controllers E5CC/E5EC Solutions Guide for FAQs
Related manuals
Contents
Document text
Digital Temperature Controllers E5CC/E5EC Solutions Guide for FAQs
Temperature E5CC/E5EC Solutions Guide for FAQs Using Basic Functions Basic Setup Procedure START CONTENTS 1. Setting the Sensor Type 2. Using ON/OFF Control 4. 3. Using PID Control 4. Setting Temperature Alarms Operation 5. Setting Heater Burnout Alarms D T C E ig em on 5 Connec t sensor and operating te rminal. Turn ON power. Setting the sensor type Using O N/OFF control Using PID control S etting th e set poin t Setting burnou heater t alarms Setting t emperature alarms
Introduction
This Solutions Guide is based on customer questions that were received at OMRON's Customer Support Center. It provides practical operating procedures for setting and changing the most common items: setting the sensor type, ON/OFF control, PID control, setting temperature alarms, and setting heater burnout alarms. Keep this Guide in a convenient location onsite to help you make settings and changes. If you are having trouble with Temperature Controller settings, this is the guidebook for you. OMRON, 2012 All rights reserved.
No part of this publication may be reproduced, stored in a retrieval system, or transmitted, in any form, or by any means, mechanical, electronic, photocopying, recording, or otherwise, without the prior written permission of OMRON. No patent liability is assumed with respect to the use of the information contained herein. Moreover, because OMRON is constantly striving to improve its high-quality products, the information contained in this manual is subject to change without notice. Every precaution has been taken in the preparation of this manual. Nevertheless, OMRON assumes no responsibility for errors or omissions.
Ne ither is any liability assumed for damages resulting from the use of the information contained in this publication. Introduction
Setting the Sensor Type
Simplicity on the Worksite Solutions Guide for FAQs: E5CC/E5EC Setting the Sensor Type Setting the Sensor Type Setting the Sensor Type Select and set the sensor type (i.e., the Input Ty pe parameter) to the set value that corresponds to the type of sensor used in the application and the required temperature range. The parameter is set to 5 (K thermocouple at − 200 to 1,300 °C) by default. Resistance Thermometers E5CC/E5EC Pt JPt Thermocouples K J T R. etc. E5CC/E5EC Any value can be set for any model. * When using the ES1B Infrared Temperature Sensor and an analog input, refer to the E5CC/E5EC Digital Temperature Controllers User's Manual (Cat. No. H174).
Simplicity on the Worksite Solutions Guide for FAQs:
E5CC/E5EC 1-1 Sensor type Input temperature setting range in °C Input temperature setting range in °F E5CC/E5EC set value Input type esistance ermomete Pt100 r JPt100 −200 to 850 °C −300 to 1500 °F 0 −199.9 to 500.0 °C −199.9 to 900.0 °F 1 0.0 to 100.0 °C 0.0 to 210.0 °F 2 −199.9 to 500.0 °C −199.9 to 900.0 °F 3 0.0 to 100.0 °C 0.0 to 210.0 °F 4 hermocoup K J T E L le U N R S B W PLII −200 to 1300 °C −300 to 2300 °F 5 (default) −20.0 to 500.0 °C 0.0 to 900.0 °F 6 −100 to 850 °C −100 to 1500 °F 7 −20.0 to 400.0 °C 0.0 to 750.0 °F 8 −200 to 400 °C −300 to 700 °F 9 −199.9 to 400.0 °C −199.9 to 700.0 °F 10 −200 to 600 °C −300 to 1100 °F 11 −100 to 850 °C −100 to 1500 °F 12 −200 to 400 °C −300 to 700 °F 13 −199.9 to 400.0 °C −199.9 to 700.0 °F 14 −200 to 1300 °C −300 to 2300 °F 15 0 to 1700 °C 0 to 3000 °F 16 0 to 1700 °C 0 to 3000 °F 17 100 to 1800 °C 300 to 3200 °F 18 0 to 2300 °C 0 to 3200 °F 19 0 to 1300 °C 0 to 2300 °F 20 ←If the setting of the Input Type parameter does not agree with the connected sensor, s.err (S.ERR:
Input Error) will flash on the display as shown at the left when the power supply is turned ON. Use the procedure on page 1-2 to set the Input Type parameter correctly.
Setting the Sensor Type
Simplicity on the Worksite Solutions Guide for FAQs: E5CC/E5EC Setting the Sensor Type Setting the Sensor Type You set this parameter in the Initial Setting Level. The parameter is set to 5 (K thermocouple at − 200 to 1,300 °C) by default. 1 Ґ Turn ON the power supply. Operating Display ← If a sensor is not connected or if the setting of the Input Type parameter does not agree w ith the connected sensor, s.err (S.ERR: Input Error) will flash on the display when the power supply is 2 turned ON. If the sensor is not connected, connect it now. Press the Ke y for at least 3 seconds. Press the ( Level) Key for at ← Flashes 3 times. least 3 seconds.
Initial Setting Level ← in-t (IN-T) will be di splayed to show that the Initial Setting Level has been entered. 3 Set the parameter with the Key s. Initial Setting Level ← in-t (IN-T): Indicates the Input Type parameter. ← Default setting is 5 (5): K thermocouple at − 200 to 1,300 °C. Initial Setting Level Change the set value with the ← Input Type: 0 (Pt100 resistance thermometer at (Up and Down) Keys. − 200 to 850 °C) (example) Set the number that you selected for the Input Type parameter on page 1-1. (When finished, press the (Level) Key for at least 1 second to return to the operation display.) Simplicity on the Worksite Solutions Guide for FAQs: E5CC/E5EC 1-2 1 Setting the Sensor Type