Simplicity on the Worksite Solutions Guide for FAQs: E5CC/E5EC Setting the Sensor Type Setting the Sensor Type Setting the Sensor Type Select and set the sensor type (i.e., the Input Ty pe parameter) to the set value that corresponds to the type of sensor used in the application and the required temperature range. The parameter is set to 5 (K thermocouple at − 200 to 1,300 °C) by default. Resistance Thermometers E5CC/E5EC Pt JPt Thermocouples K J T R. etc. E5CC/E5EC Any value can be set for any model. * When using the ES1B Infrared Temperature Sensor and an analog input, refer to the E5CC/E5EC Digital Temperature Controllers User's Manual (Cat. No. H174).
Simplicity on the Worksite Solutions Guide for FAQs:
E5CC/E5EC 1-1 Sensor type Input temperature setting range in °C Input temperature setting range in °F E5CC/E5EC set value Input type esistance ermomete Pt100 r JPt100 −200 to 850 °C −300 to 1500 °F 0 −199.9 to 500.0 °C −199.9 to 900.0 °F 1 0.0 to 100.0 °C 0.0 to 210.0 °F 2 −199.9 to 500.0 °C −199.9 to 900.0 °F 3 0.0 to 100.0 °C 0.0 to 210.0 °F 4 hermocoup K J T E L le U N R S B W PLII −200 to 1300 °C −300 to 2300 °F 5 (default) −20.0 to 500.0 °C 0.0 to 900.0 °F 6 −100 to 850 °C −100 to 1500 °F 7 −20.0 to 400.0 °C 0.0 to 750.0 °F 8 −200 to 400 °C −300 to 700 °F 9 −199.9 to 400.0 °C −199.9 to 700.0 °F 10 −200 to 600 °C −300 to 1100 °F 11 −100 to 850 °C −100 to 1500 °F 12 −200 to 400 °C −300 to 700 °F 13 −199.9 to 400.0 °C −199.9 to 700.0 °F 14 −200 to 1300 °C −300 to 2300 °F 15 0 to 1700 °C 0 to 3000 °F 16 0 to 1700 °C 0 to 3000 °F 17 100 to 1800 °C 300 to 3200 °F 18 0 to 2300 °C 0 to 3200 °F 19 0 to 1300 °C 0 to 2300 °F 20 ←If the setting of the Input Type parameter does not agree with the connected sensor, s.err (S.ERR:
Input Error) will flash on the display as shown at the left when the power supply is turned ON. Use the procedure on page 1-2 to set the Input Type parameter correctly.