Simplicity on the Worksite Solutions Guide for FAQs: E5CC/E5EC Setting Temperature Alarms Ava ilable Alarm Types You select the alarm type according to the required conditions. ⇒ ⇒ ⇒ ⇒ ⇒ Setting Temperature Alarms ⇒ ⇒ ⇒ Simplicity on the Worksite Solutions Guide for FAQs: E5CC/E5EC 4-3 Do you want to link the alarm temperature to the set point? Do you need a standby sequence? In what cases do you want to output an alarm? - - None Alarm Type Operation No. Name Set this number in the Temperature Controller You use these numbers for the following Alarm Type parameters: alt1 (ALT1), alt2 (ALT2), alt3 (ALT3), and alt4 (ALT4). Refer to page 4-6 for the procedure.

0 No alarm Set this alarm type when you do not need an alarm. 1 Upper-limit and Lower-limit Alarm ON ON ON OFF Temperature SP Lower limit value Upper limit value 2 Upper-limit Alarm ON ON OFF Temperature SP Upper limit value 3 Lower-limit Alarm ON ON OFF Temperature SP Lower limit value 4 Upper-limit and Lower-limit Range Alarm ON ON OFF Temperature SP Lower limit value Upper limit value 5 Upper-limit and Lower-limit Alarm with Standby Sequence ON ON ON OFF Temperature SP Lower limit value Upper limit value 6 Upper-limit Alarm with Standby Sequence ON ON OFF Temperature SP Upper limit value 7 Lower-limit Alarm with Standby Sequence ON ON OFF Temperature SP Lower limit value