Mitsubishi — 3.11.2 Alarm Setup

Chapter 3 Creating and Editing Screens 3.11.2 Alarm Setup The user can set alarm by clicking Options > Alarm Setup . The alarm setup should set with the alarm function in element settings. HMI will execute alarm function automatically if both settings are all set. When the specified conditions are matched (If condition occurs in specific address, ON enabled or OFF enabled) after setting, HMI will display an Alarm Setup warning dialog box automatically. In this dialog box (Fig. 3-11-1), there are Delete, Modify, Import, Export and OK buttons for the user to use. Fig.

3-11-1 Alarm Setup dialog box Revision May, 2010 3-237 Alarm Setup Dialog Box Alarm Setting Address Use this option to set the alarm starting address. It provides 512 alarms, 32 Words. Please note that the unit of this address is Word. If the connecting controller is Delta PLC, when the register type is M or S, the address must be 0 or the multiple of 16, i.e. M0 and M16. If the address is M1, system will determine it is an invalid address. Scan Time (second)(秒) Set how long it takes for the HMI to scan one time. The unit is seconds.