Mitsubishi — 3.11.2 Alarm Setup

Chapter 3 Creating and Editing Screens 3-238 Revision May, 2010 Alarm Setup Dialog Box Alarm Setting Max. Records Use this option to retain a specific number of records. When the number of records exceeds this setting value, HMI will delete the first record and insert the new record into the last address. For example, if the setting value is set to 100 and the number of records in history exceeds 100, the first record is deleted and the second record will become to the third record, the third record will become to the forth record…and the 100th record will become to 99th record. The new record (101st record) becomes the 100th record.

Hold (Non-volatile) Using this option saves data in SRAM when the power is turned off. The capacity for saving alarm data of DOP-B series is 4Kbytes. The battery of the SRAM provides power when the power is turned off. (In some DOP-B series models, the user can save data in USB disk or CF card when the power is turned off and the capacity for saving alarm data depends on the capacity of the USB disk or CF card.) CSV Format Using this option saves data in CSV format. Alarm Property Setup The user can double click a row of the alarm message contents table to edit the alarm property and press Modify button to change it.

(Please note that there are three languages tabs in Alarm Setup dialog box as the multi-language function is also supported here. The user can click the tab to edit the alarm message contents according to the user’s requirement.)