Chapter 3 Creating and Editing Screens Revision May, 2010 3-239 Alarm Setup Dialog Box Alarm Setting Alarm Property Setup The following Alarm Property Setup dialog box will display after double clicking the row. Message Display message when an alarm occurs. Color Display message color when an alarm occurs. Alarm Property Setup Use this option to determine if the Bit is On or Off when an alarm occurs. Goto Screen Display screen when an alarm occurs. Delete Delete the alarm message contents. Modify Modify the alarm message contents. The user also can double click the mouse to perform this function. Import Import the Alarm Describe File into the alarm message contents table.

Export Export the alarm message contents from HMI and convert them to be Alarm Describe File. OK End the editing of alarm message contents. The calculation method of the size of the alarm history file is as follows: 6Bytes(a)2Bytes(b)N(c)6Bytes(d)ActualFileSize Bytes a Time and Date Data b Alarm Data c Sampling Points d Data File Symbol Example: If Max. Records is set to 100, and the time and date is recorded, the required capacity for saving alarm data is: [(6 Bytes + 2 Bytes) × 100] + 6 Bytes= 806 Bytes If Max. Records is set to 100, and the time and date is not recorded, the required capacity for saving alarm data is:

(2 Bytes × 100) + 6 Bytes = 206 Bytes a Time and Date Data b Alarm Data c Sampling Points d Data File Symbol