Mitsubishi — 3.14.3.8 Communication

Chapter 3 Creating and Editing Screens Var2 Settings in INITCOM (Communication Protocol) Revision May, 2010 3-355 Item Type Code Remark COM Port COM1 0 COM2 1 COM3 2 Communication Interface RS232 0 RS422 1 RS485 2 Data Bit 7 Bits 0 8 Bits 1 Parity Bit None 0 Odd 1 Even 2 Stop Bit 1 Bits 0 2 Bits 1 Baud Rate 300 0 600 1 900 2 1200 3 2400 4 4800 5 9600 6 14400 7 19200 8 28800 9 38400 10 57600 11 115200 12 Flow Control No Flow Control 0 Please refer to the following descriptions. CTS RTS Flow Control 1 DTR DSR Flow Control 2 Xon Xoff Flow Control 3