Chapter 3 Creating and Editing Screens Clearing History Buffer Register (HBCR) The history buffer when controlled by a PLC can also be cleared by the PLC. Clearing History Buffer Flag Bits 0 to 11 clear the history buffer. When this flag is turned ON, HMI clears the history buffer one time. To control the clearing history buffer flag again, this flag must be turned OFF and then ON again. Recipe Control Register (RECR) Change Recipe Number Flag To change recipe number, the user can use Recipe Number Register RCPNO directly or use this flag. To specify the recipe number, write the recipe number into the Recipe Number Designation Register (RBIR) and then turn ON this flag (Bit 0).
After the above 3-32 Revision May, 2010 Corresponding Flag Corresponding Binary Display of Relative Buffer Area Bit Function Position (x) Buffer Area 1 0 0000 0000 0000 000x Clearing History Buffer Flag 1 Buffer Area 2 1 0000 0000 0000 00x0 Clearing History Buffer Flag 2 Buffer Area 3 2 0000 0000 0000 0x00 Clearing History Buffer Flag 3 Buffer Area 4 3 0000 0000 0000 x000 Clearing History Buffer Flag 4 Buffer Area 5 4 0000 0000 000x 0000 Clearing History Buffer Flag 5 Buffer Area 6 5 0000 0000 00x0 0000 Clearing History Buffer Flag 6 Buffer Area 7 6 0000 0000 0x00 0000 Clearing History Buffer Flag 7 Buffer Area 8 7 0000 0000 x000 0000 Clearing History Buffer Flag 8 Buffer Area 9 8 0000 000x 0000 0000 Clearing History Buffer Flag 9 Buffer Area 10 9 0000 00x0 0000 0000 Clearing History Buffer Flag 10 Buffer Area 11 10 0000 0x00 0000 0000 Clearing History Buffer Flag 11 Buffer Area 12 11 0000 x000 0000 0000 Clearing History Buffer Flag 12 12-15 xxxx 0000 0000 0000 Reserved Binary Display of Relative Bit Function Position (x) 0 0000 0000 0000 000x Change Recipe Number Flag 1 0000 0000 0000 00x0 Read Recipe Flag (PLC → HMI):
Read recipe data from PLC and store it in HMI 2 0000 0000 0000 0x00 Write Recipe Flag (PLC ← HMI) Write recipe data from HMI into PLC 3 0000 0000 0000 x000 Change Recipe Group Number Flag 4-7 0000 0000 xxxx 0000 Reserved 8-15 xxxx xxxx 0000 0000 Designate Recipe Group Number