3. Instruction Set Ladder diagram: Instruction: Operation: LD X1 Load NO contact X1 ANI X15F4 Connect NC contact X11 in series OUT Y1 Drive Y1 coil (Suppose F4=K-4) Explanations: 1. The OR instruction is used to connect NO contact in parallel. 2. DVP-ES2/EX2 series PLCs whose version is 3.20/DVP-SS2 series PLCs whose version is 3.00/DVP-SA2 series PLCs whose version is 2.60/DVP-SE series PLCs whose version is 1.20/DVP-SX2 series PLCs whose version is 2.40 (and above) support the operands X, Y, M, and S. These operands can be qualified by E or F. Users have to use WPLSoft version 2.31 (or above)/ISPSoft version 2.01 (or above). Program example: Ladder diagram: Instruction: Operation:
X1 Y1 X0 LD X0 Load NO contact X0 OR X1 Connect NO contact X1 in parallel OUT Y1 Drive Y1 coil Ladder diagram: Instruction: Operation: X0 Y1 LD X0 Load NO contact X0 OR X0F1 Connect NO contact X5 in parallel (Suppose F1=K5) OUT Y1 Drive Y1 coil Explanations: 1. The ORI instruction is used to connect NC contact in parallel. 2. DVP-ES2/EX2 series PLCs whose version is 3.20/DVP-SS2 series PLCs whose version is 3.00/DVP-SA2 series PLCs whose version is 2.60/DVP-SE series PLCs whose version is 1.20/DVP-SX2 series PLCs whose version is 2.40 (and above) support the operands X, Y, M, and S. These operands can be qualified by E or F.
Users have to use WPLSoft version 2.31 (or above)/ISPSoft version 2.01 (or above). 3-5 X1 LDI X15F4 Y1 Mnemonic Operands Function Program steps Controllers SA2 ES2/EX2 SS2 SX2 SE OR X, Y, M, S, T, C Connect NO contact in parallel 1~3 Controllers SA2 ES2/EX2 SS2 SX2 SE LD X0F1 Mnemonic Operands Function Program steps Controllers SA2 ES2/EX2 SS2 SX2 SE ORI X, Y, M, S, T, C Connect NC contact in parallel 1~3 Controllers SA2 ES2/EX2 SS2 SX2 SE