Delta DVP-ES2 — 3.2 Explanations to Basic Instructions

DVP-ES2/EX2/SS2/SA2/SX2/SE&TP Operation Manual - Programming Program example: Ladder diagram: Instruction: Operation: X1 Y1 X0 LD X0 Load NO contact X0 ORI X1 Connect NC contact X1 in parallel OUT Y1 Drive Y1 coil Ladder diagram: Instruction: Operation: X0 Y1 LD X0 Load NO contact X0 ORI X7E6 Connect NC contact X4 in parallel (Suppose E6=K-3) OUT Y1 Drive Y1 coil Explanations: The ANB instruction is used to connect a circuit block to the preceding block in series. Generally, the circuit block to be connected in series consists of several contacts which form a parallel connection structure. Program example: Ladder diagram: Instruction: Operation:

X0 ANB X1 LD X0 Load NO contact X0 ORI X2 Connect NC contact X2 in parallel LDI X1 Load NC contact X1 Block A Block B OR X3 Connect NO contact X3 in parallel ANB Connect circuit block in series OUT Y1 Drive Y1 coil Explanations: The ORB instruction is used to connect a circuit block to the preceding block in parallel. Generally, the circuit block to be connected in parallel consists of several contacts which form a serial connection structure. 3-6 LDI X7E6 Mnemonic Function Program steps Controllers ANB Connect a block in series 1 ES2/EX2 SS2 SA2 SX2 SE Y1 Mnemonic Function Program steps Controllers SA2 ES2/EX2 SS2 SX2 SE Controllers ORB Connect a block in parallel 1 SA2 ES2/EX2 SS2 SX2 SE