Delta DVP-ES2 — 3.2 Explanations to Basic Instructions

DVP-ES2/EX2/SS2/SA2/SX2/SE&TP Operation Manual - Programming Program example: Ladder diagram: Instruction: Operation: X0 Y1 X1 MPS LD X0 Load NO contact X0 M0 X2 AND X1 Connect NO contact X1 in series MPS Store current status MRD OUT Y1 Drive Y1 coil Y2 MRD Read the stored status END MPP AND X2 Connect NO contact X2 in series OUT M0 Drive M0 coil MPP Read the stored status and reset OUT Y2 Drive Y2 coil END End of program Note: When compiling ladder diagram with WPLSoft, MPS, MRD and MPP will be automatically added to the compiled results in instruction format. However, users programming in instruction mode have to enter branch instructions as required. Explanations: 1.

Output the program evaluation results before OUT instruction to the designated device. 2. DVP-ES2/EX2 series PLCs whose version is 3.20/DVP-SS2 series PLCs whose version is 3.00/DVP-SA2 series PLCs whose version is 2.60/DVP-SE series PLCs whose version is 1.20/DVP-SX2 series PLCs whose version is 2.40 (and above) support the operands Y, M, and S. These operands can be qualified by E or F. Users have to use WPLSoft version 2.31 (or above)/ISPSoft version 2.01 (or above). Status of coil contact Program example: Ladder diagram: Instruction: Operation:

X0 X1 Y1 LDI X0 Load NC contact X0 AND X1 Connect NO contact X1 in series OUT Y1 Drive Y1 coil 3-8 Mnemoni c Operands Function Program steps Controllers OUT Y, M, S Output coil 1~3 SA2 ES2/EX2 SS2 SA2 SE OUT instruction Evaluation result Associated Contacts Coil NO contact(normal open) NC contact(normal close) FALSE OFF Current blocked Current flows TRUE ON Current flows Current blocked