Delta DVP-ES2 — 3.8 Detailed Instruction Explanation

3. Instruction Set 2. When the instruction MC is executed, the previous state of the switch contact is put onto the top of the stack inside the PLC. The stack is controlled by the PLC, and can not be changed by users. When the instruction MCR is executed, the previous state of the switch contact is popped from the top of the stack. Under the conditions listed in (b), (d), and (e) above, the number of times the items are pushed onto the stack may be different from the number of times the items are popped from the stack. When this situation occurs, at most 32 items can be pushed onto the stack, and the items can be popped form the stack until the stack is empty.

Therefore, when CJ or CJP is used with MC and MCR, users have to be careful of the pushing of the item onto the stack and the popping of the item from the stack. Program example 3: The table explains the device status in the ladder diagram below. *1: Y1 is dual output. When M0 is OFF, it is controlled by M1. When M0 is ON, M12 will control Y1 *2: When timer that subroutine used (T184~T199) executes first and then CJ instruction is executed, the timer will keep counting. After the timer reaches the set value, output contact of timer will be ON. *3:

When high-speed counters (C235~C254) executes first and then CJ instruction is executed, the counter will keep counting and its associated output status remains. 3-43 Contact state Contact state Output coil state Device before CJ execution during CJ execution during CJ execution Y, M, S M1, M2, M3 OFF M1, M2, M3 OFF→ON Y1 *1, M20, S1 OFF M1, M2, M3 ON M1, M2, M3 ON→OFF Y1 *1, M20, S1 ON 10ms, 100ms Timer*2 M4 OFF M4 OFF→ON Timer is not activated M4 ON M4 ON→OFF Timer T0 immediately stops and is latched. When M0 ON  OFF, T0 will be reset. 1ms,10ms, 100ms accumulative Timer M6 OFF M6 OFF→ON Timer T240 is not activated M6 ON M6 ON→OFF Timer T240 immediately stops and is latched.

When M0 ON  OFF, T240 will still be latched. C0~C234 *3 M7, M10 OFF M10 is ON/OFF triggered Counter C0 stops M7 OFF, M10 is ON/OFF triggered M10 is ON/OFF triggered Counter C0 stops and latched. When M0 is OFF, C0 resumes counting. Application instruction M11 OFF M11 OFF→ON Application instructions will not be executed. M11 ON M11 ON→OFF The skipped application instruction will not be executed but API 53~59, API 157~159 keep executing.