Delta DVP-ES2 — 3.8 Detailed Instruction Explanation

DVP-ES2/EX2/SS2/SA2/SX2/SE&TP Operation Manual - Programming Operands: S : Source of data D : Destination of data n : Number of data to be moved Explanations: 1. The contents in n registers starting from the device designated by S will be moved to n registers starting from the device designated by D . If n exceeds the actual number of available source devices, only the devices that fall within the valid range will be used 2. If operand S use index register F, only 16-bit instruction is available 3. The range of n: 1~ 512 Program example:

When X20 = ON, K10 will be moved to the 5 consecutive registers starting from D10 X20 K5 K10 D10 K10 K10 D11 K10 D12 n=5 K10 D13 K10 D14 3-68 API Mnemonic Operands Function Controllers 16 D FMOV P Fill Move ES2/EX2 SS2 SA2 SX2 SE Type OP Bit Devices Word devices Program Steps X Y M S K H KnX KnY KnM KnS T C D E F FMOV, FMOVP: 7 steps DFMOV, DFMOVP: 13 steps S * * * * * * * * * * * D * * * * * * n * * PULSE 16-bit 32-bit SA2 SX2 SS2 SA2 SA2 ES2/EX2 SS2 ES2/EX2 SX2 ES2/EX2 SS2 SX2 SE SE SE FMOV K10 D10