DVP-ES2/EX2/SS2/SA2/SX2/SE&TP Operation Manual - Programming Operands: D : Destination device Explanation: 1. If the instruction is not used in pulse execution mode, the content in the designated device D will minus “1” in every scan whenever the instruction is executed. 2. This instruction is generally used in pulse execution mode (DECP, DDECP). 3. In 16-bit instruction, if –32,768 is reached and “1” is minused, it will write a value of +32,767 to the destination. In 32-bit instruction, if -2,147,483,648 is reached and “1” is minused, it will write a value of +2,147,483,647 to the destination. 4. If operand D uses index F, only a 16-bit instruction is applicable. 5.
The operation results will not affect M1020 ~ M1022 Program Example: When X0 is triggered, the value in D0 will be decremented by 1. X0 3-82 API Mnemonic Operands Function Controllers SA2 ES2/EX2 SS2 SX2 SE Controllers 25 D DEC P Decrement SA2 ES2/EX2 SS2 SE SX2 Type OP Bit Devices Word devices Program Steps X Y M S K H KnX KnY KnM KnS T C D E F DEC, DECP: 3 steps DDEC, DDECP: 5 steps D * * * * * * * * PULSE 16-bit 32-bit SA2 SS2 SA2 SA2 SX2 ES2/EX2 SS2 SX2 ES2/EX2 SX2 ES2/EX2 SS2 SE SE SE DECP D0