DVP-ES2/EX2/SS2/SA2/SX2/SE&TP Operation Manual - Programming API 31 Operands: D : Device to be rotated n : Number of bits to be rotated in 1 rotation Explanation: 2. The status of the last bit rotated (marked with ※ ) is copied to the carry flag M1022. 1. This instruction rotates bit status of the device D to the left for n bits 3. This instruction is generally used in pulse execution mode (ROLP, DROLP). 4. If operand D uses index F, only a 16-bit instruction is available. 5. If operand D is specified as KnY, KnM or KnS, only K4 (16-bit) or K8 (32-bit) is valid. 6. Valid range of operand n : 1≤ n ≤16 (16-bit), 1≤ n ≤32 (32-bit) Program Example:
When X0 goes from OFF to ON, all the 16 bits (4 bits as a group) in D10 will rotate to the left, as shown in the figure below. The bit marked with ※ will be sent to carry flag M1022. X0 Rotate to the left Upper bit Lower bit M1022 D10 Carry flag 16 bits After one rotation to the left Upper bit Lower bit M1022 Carry flag 1 D10 3-92 Mnemonic Operands Function Controllers SA2 ES2/EX2 SS2 SX2 SE Controllers D ROL P Rotate Left ES2/EX2 SS2 SA2 SX2 SE Type OP Bit Devices Word devices Program Steps X Y M S K H KnX KnY KnM KnS T C D E F ROL, ROLP: 5 steps DROL, DROLP:
9 steps D * * * * * * * * n * * PULSE 16-bit 32-bit SA2 SE SX2 SS2 SA2 SA2 SX2 ES2/EX2 SS2 ES2/EX2 SX2 ES2/EX2 SS2 SE SE ROLP D10 K4 1 1 1 1 1 1 1 1 0 0 0 0 0 0 0 0 1 1 1 1 0 0 0 0 0 0 0 0 1 1 1 1