Delta DVP-ES2 — 3.8 Detailed Instruction Explanation

DVP-ES2/EX2/SS2/SA2/SX2/SE&TP Operation Manual - Programming API 33 Operands: D : Device to be rotated n : Number of bits to be rotated in 1 rotation Explanations: 2. The status of the last bit rotated (marked with ※ ) is moved to the carry flag M1022. 1. This instruction rotates bit status of the device D together with M1022 to the left for n bits. 3. This instruction is generally used in pulse execution mode (RCLP, DRCLP). 4. If operand D uses index F, only a 16-bit instruction is available. 5. If operand D is specified as KnY, KnM or KnS, only K4 (16-bit) or K8 (32-bit) is valid. 6. Valid range of operand n : 1≤ n ≤16 (16-bit), 1≤ n ≤32 (32-bit) Program Example:

When X0 goes from OFF to ON, the 16 bits (4 bits as a group) in D10 together with carry flag M1022 (total 17 bits) will rotate to the left, as shown in the figure below. The bit marked with ※ will be sent to carry flag M1022. X0 Rotate to the left Upper bit Lower bit M1022 0 D10 Carry flag 16 bits After one rotation to the left Upper bit Lower bit M1022 Carry flag 1 D10 3-94 Mnemonic Operands Function Controllers SA2 ES2/EX2 SS2 SX2 SE D RCL P Rotation Left with Carry SS2 SA2 SX2 SE Type OP Bit Devices Word devices Program Steps X Y M S K H KnX KnY KnM KnS T C D E F RCL, RCLP: 5 steps DRCL, DRCLP:

9 steps D * * * * * * * * n * * PULSE 16-bit 32-bit SA2 SS2 SA2 SX2 SA2 SX2 ES2/EX2 SS2 SX2 ES2/EX2 ES2/EX2 SS2 SE SE SE RCLP D10 K4 1 1 1 1 1 1 1 1 0 0 0 0 0 0 0 1 1 1 1 0 0 0 0 0 0 0 0 0 1 1