DVP-ES2/EX2/SS2/SA2/SX2/SE&TP Operation Manual - Programming as the source counter automatically and no syntax check error will be detected. Designers have to specify the comparison value of a hardware comparator before they enable a comparison instruction. If the comparison value of a hardware comparator has to be changed after a comparison instruction is enabled, it is suggested that users should disable the comparison instruction first. After the users specify a new comparison value, the users can enable the comparison instruction again.
If users want to change the value of a hardware comparator without disabling the high-speed comparison instruction which is being used, they have to check whether the model used support this operation. The models which support this operation are listed below. Note: If the comparative value changes, it will not be stored in the hardware comparator until the instruction is scanned. Table of settings for the high-speed interrupts of hardware counters and comparators: (It is not applicable to DVP-12SE.) Table of settings for the high-speed interrupts of hardware counters and comparators:
(It is only applicable to DVP-12SE.) 3-128 Model name ES2/EX2 SS2 SA2 SX2 SE Version V3.20 and above V3.00 and above V2.60 and above V2.40 and above V1.00 and above A group B group Hardware counter A1 A2 A3 A4 B1 B2 B3 B4 Counter No. C243, C245~C248, C251,C252 C244, C249, C250, C253, C254 High-speed counter I010 I020 I030 I040 I050 I060 I070 I080 interrupt High-speed compare Share 4 hardware comparators for group A Share 4 hardware comparators for group B Set/Reset A group B group Hardware counter A1 A2 B1 B2 Counter No.
C243, C245~C248, C251,C252 C244 High-speed counter I010 I020 I050 I060 interrupt Hi-speed compare Share 2 hardware comparators for group A Share 2 hardware comparators for group B Set/Reset