Delta DVP-ES2 — 3.8 Detailed Instruction Explanation

3. Instruction Set 6. Four pulse output modes: (They are only applicable to DVP-12SE.) 7. Pulse output flags: a) M1029 = ON after Y0/Y1 (D1220=K1, pulse/Dir) output is completed. M1102 = ON after Y2/Y3 (D1221=K1, pulse/Dir) output is completed. M1029 = ON after the Y0/Y2 (D1220 = K3, CW/CCW) output is completed. b) The execution completed flag M1029, M1030, M1102, and M1103 should be manually reset by users after pulse output is completed. c) When PLSY / DPLSY instruction is OFF, the pulse output completed flags will all be reset. d) When M1190~M1193 = ON, the available output range for PLSY Y0~Y3 is 0.01~10Hz. 8.

While the PLSY instruction is being executed, the output will not be affected if S 2 is changed. To change the pulse output number, stop the PLSY instruction, then change the pulse number. 9. S 1 can be changed during program execution and the change will take effects until the modified PLSY instruction is being executed. 10. The ratio of OFF time and ON time of the pulse output is 1:1. 11. If operand S 1 , S 2 use index F, only 16-bit instruction is available. 12. There is no limitation on the times of using this instruction, however the program allows only 4 instructions (PLSY, PWM, PLSR) to be executed at the same time.

If Y1 is used for several high speed pulse output instructions, PLC will output according to the execution order of these instructions. Program Example: 1. When X0 = ON, 200 pulses of 1kHz are generated from output Y0, after the pulse output has been completed, M1029 = ON to set Y20. 2. When X0 = OFF, pulse output Y0 will immediately stop. When X0 turns ON again, the pulse output will start from the first pulse. 3-141 D1220 D1221 Mode K0 K1 K3# K0 K1 K3# Output Y0 Pulse Pulse CW Y1 Pulse Dir Pulse Y2 Pulse Pulse CCW Y3 Pulse Dir Pulse Output device Y0 Y1 Y2 Y3 Completed Flag M1029 M1030 M1102 M1103 Immediately pause M1078 M1079 M1104 M1105 0.01~10Hz output M1190 M1191 M1192 M1193