Delta DVP-ES2 — 3.8 Detailed Instruction Explanation

3. Instruction Set 58 Operands: S 1 : Pulse output width (ms) S 2 : Pulse output cycle (ms) D : Pulse output device (Y0, Y1, Y2,Y3) Explanations: 1. S 1 is specified as pulse output width (t). S 2 is specified as pulse output cycle (T). Rule: S1 ≦ S2 . (It is not applicable to DVP-12SE.) 2. S 1 is specified as pulse output width (t). S 2 is specified as pulse output cycle (T). Rule: S1 ≦ S2 . (It is only applicable to DVP-12SE.) 3. Pulse output devices for operand D: Y0, Y1, Y2, Y3, 4. When several pulse output instructions (PLSY, PWM, PLSR) use Y1 or Y3 as the output device in the same scan cycle, PLC will perform the instruction which is executed first. 5.

When S 1 0, ≦ S 2 0 or ≦ S 1 > S 2 , errors will occur (M1067 and M1068 will not be ON) and no output will be generated from pulse output devices. When S 1 = S 2 , the pulse output device will be ON continuously. 6. S 1 , S 2 can be changed when PWM instruction is being executed. 7. When M1112 = ON, the unit of Y0 output pulse is 10μs, when M1112 = OFF, the unit is 100μs. 8. When M1070 = ON, the unit of Y1 output pulse is 100μs, when M1070 = OFF, the unit is 1ms. 9. When M1113 = ON, the unit of Y2 output pulse is 10μs, when M1113 = OFF, the unit is 100μs. (It is not applicable to DVP-12SE.) 10. When M1113 = ON, the unit of Y2 output pulse is 100μs, when M1113 = OFF, the unit is 1ms.

(It is only applicable to DVP-12SE.) 3-145 Mnemonic Operands Function Controllers PWM Pulse Width Modulation ES2/EX2 SS2 SA2 SX2 SE Type OP Bit Devices Word devices Program Steps X Y M S K H KnX KnY KnM KnS T C D E F PWM: 7 steps S 1 * * * * * * * * * * * S 2 * * * * * * * * * * * D * PULSE 16-bit 32-bit ES2/EX2 SS2 SA2 SE SX2 SA2 SA2 ES2/EX2 SS2 SX2 ES2/EX2 SS2 SX2 SE SE Reference Table for Output Cycle and Output Width Range of pulse output width / cycle Output Y0 Y2 Y1 Y3 t 0~10000 0~32767 T 1~10000 1~32,767 Flag for switching unit M1112 M1113 M1070 M1071 Flag for high-speed output M1116 is ON. (Unit: 1us) M1117 is ON. (Unit:

10us) Reference Table for Output Cycle and Output Width Range of pulse output width / cycle Output Y0 Y1 Y2 Y3 t 0~10000 0~32767 T 1~10000 1~32767 Flag for switching unit M1112 M1070 M1113 M1071