DVP-ES2/EX2/SS2/SA2/SX2/SE&TP Operation Manual - Programming API 78 Operands: data n : Number of data to be read at a time m 1 : No. of special module m 2 : CR# in special module to be read D : Device for storing read Explanations: 1. PLC uses this instruction to read CR (Control register) data from special modules. 2. Operand ranges for m1 , m2 , and n : ES2/EX2: SA2/SX2: *The maximum number of values which can be read by SA2 V2.6/SX2 V2.4 (below) is 4 (16-bit instruction/2 (32-bit instruction). SE:
3-216 Mnemonic Operands Function Controllers ES2/EX2 SS2 SA2 SX2 SE D FROM P Read CR data from Special Modules Controllers ES2/EX2 SS2 SA2 SX2 SE Type OP Bit Devices Word devices Program Steps X Y M S K H KnX KnY K nM KnS T C D E F FROM, FROMP: 9 steps DFROM, DFROMP: 17 steps m 1 * * * m 2 * * * D * n * * * PULSE 16-bit 32-bit SA2 SA2 SA2 ES2/EX2 S S2 SX2 ES2/EX2 SS2 SX2 ES2/EX2 SS2 SX2 SE SE SE Operand m1 m2 n in the 16-bit instruction n in the 32-bit instruction Right-side module 0~7 0~255 1~4 1~6 (ES2/EX2 V3.0 and above) 1~2 1~3 (ES2/EX2 V3.0 and above) Left-side module Left-side modules are not supported.
Operand m1 m2 n in the 16-bit instruction n in the 32-bit instruction Right-side module 0~7 0~48 1~6* 1~3* Left-side module 100~107 0~255 1~(256-m2) 1~(256-m2)/2 Operand m1 m2 n in the 16-bit instruction n in the 32-bit instruction Right-side module 0~7 0~48 1~4 1~6 (SE V1.4 and above) 1~2 1~3 (SE V1.4 and above) Left-side module 100~108 0~255 1~(256-m2) 1~(256-m2)/2