Delta DVP-ES2 — 3.8 Detailed Instruction Explanation

3. Instruction Set SS2: Program Example: 1. Read out the data in CR#29 of special module N0.0 to register D0 in PLC, and CR#30 of special module No.0 to register D1 in PLC. 2 consecutive 16-bit data are read at one time ( n = 2). 2. When X0 = ON, the instruction executes; when X0 = OFF, the previous content in D0 and D1 won’t be changed. X0 3-217 Operand m1 m2 n in the 16-bit instruction n in the 32-bit instruction Right-side module 0~7 0~48 1~4 1~6 (SS2 V2.8 and above) 1~2 1~3 (SS2 V2.8 and above) Left-side module Left-side modules are not supported. FROM K0 K29 D0 K2