DVP-ES2/EX2/SS2/SA2/SX2/SE&TP Operation Manual - Programming Sending data: (PLC→External equipment) Source data register, starting from lower 8 bits of D100 Length = 4 Receving data: (External equipment→PLC) Points to note: 1. PLC COM1 RS-232: Associated flags (Auxiliary relays) and special registers (Special D) for communication instructions RS / MODRD 3-228 D100L D101L D102L D103L D120L D121L D122L D123L D124L D125L D126L Registers for received data, starting from lower 8 bits of D120 Length = 7 Flag Function Action M1138 COM1 retain communication settings. Communication settings will be reset (changed) according to the content in D1036 after every scan cycle.
Users can set ON M1138 if the communication protocol requires to be retained. When M1138 = ON, communication settings will not be reset (changed) when communication instructions are being processed, even if the content in D1036 is changed. Supported communication instructions: RS / MODRW User sets and resets M1139 COM1 ASCII / RTU mode selection, ON: RTU mode, OFF: ASCII mode. Supported communication instructions: RS / MODRW User sets and resets M1312 COM1 sending request. Before executing communication instructions, users need to set M1312 to ON by trigger pulse, so that the data sending and receiving will be started. When the communication is completed, PLC will reset M1312 automatically.
Supported communication instructions: RS / MODRW User sets and system resets M1313 COM1 data receiving ready. When M1313 is ON, PLC is ready for data receiving Supported communication instructions: RS / MODRW System