3. Instruction Set 2. PLC COM2 RS-485: Associated flags (Auxiliary relays) and special registers (Special D) for communication instructions RS / MODRD / MODWR / FWD / REV / STOP / RDST / RSTEF / MODRW. 3-229 Flag Function Action M1314 COM1 Data receiving completed. When data receiving of communication instructions is completed, M1314 will be ON. Users can process the received data when M1314 is ON. When data processing is completed, M1314 has to be reset by users. Supported communication instructions: RS / MODRW System sets and user resets M1315 COM1 receiving error. M1315 will be set ON when errors occur and the error code will be stored in D1250. Supported communication instructions:
RS / MODRW System sets and user resets Special register Function D1036 COM1 (RS-232) communication protocol. Refer to the following table in point 4 for protocol setting. D1167 The specific end word to be detected for RS instruction to execute an interruption request (I140) on COM1 (RS-232). Supported communication instructions: RS D1121 COM1 (RS-232) and COM2 (RS-485) communication address. D1249 COM1 (RS-232) Communication time-out setting (unit: ms). If users set up time-out value in D1249 and the data receiving time exceeds the time-out value, M1315 will be set ON and the error code K1 will be stored in D1250. M1315 has to be reset manually when time-out status is cleared.
D1250 COM1 (RS-232) communication error code. Supported communication instructions: MODRW Flag Function Action M1120 Retain communication settings. Communication settings will be reset (changed) according to the content in D1120 after every scan cycle. Users can set ON M1120 if the communication protocol requires to be retained. When M1120 = ON, communication settings will not be reset (changed) when communication instructions are being processed, even if the content in D1120 is changed. User sets/resets