DVP-ES2/EX2/SS2/SA2/SX2/SE&TP Operation Manual - Programming 3-230 Flag Function Action M1121 Data transmission ready. M1121 = OFF indicates that RS-485 in COM2 is transmitting System sets M1122 Sending request. Before executing communication instructions, users need to set M1122 to ON by trigger pulse, so that the data sending and receiving will be started. When the communication is completed, PLC will reset M1122 automatically. User sets, system resets M1123 Data receiving completed. When data receiving of communication instructions is completed, M1123 will be ON. Users can process the received data when M1123 is ON. When data processing is completed, M1123 has to be reset by users.
Supported communication instructions: RS System sets ON and user resets M1124 Data receiving ready. When M1124 is ON, PLC is ready for data receiving.. System sets M1125 Communication ready status reset. When M1125 is set ON, PLC resets the communication (transmitting/receiving) ready status. M1125 has to be reset by users after resetting the communication ready status. User sets/resets M1126 Set STX/ETX as user-defined or system-defined in RS communication. For details please refer to the table in point 5. M1126 only supports RS instruction. M1130 Set STX/ETX as user-defined or system-defined in RS communication. For details please refer to the table in point 5.
M1130 only supports RS instruction M1127 COM2 (RS-485) data sending/receiving/converting completed. RS instruction is NOT supported. Supported communication instructions: MODRD / MODWR / FWD / REV / STOP / RDST / RSTEF / MODRW System sets and user resets M1128 Transmitting/receiving status indication. System sets M1129 Receiving time out. If users set up time-out value in D1129 and the data receiving time exceeds the time-out value, M1129 will be set ON. System sets and user resets