Delta DVP-ES2 — 3.8 Detailed Instruction Explanation

3. Instruction Set 3-231 Flag Function Action M1131 In ASCII mode, M1131 = ON only when MODRD/RDST/MODRW data is being converted to HEX. Supported communication instructions: MODRD / RDST / MODRW System sets M1140 MODRD/MODWR/MODRW data receiving error Supported communication instructions: MODRD / MODWR / MODRW M1141 MODRD/MODWR/MODRW parameter error Supported communication instructions: MODRD / MODWR/ MODRW M1142 Data receiving error of VFD-A handy instructions. Supported communication instructions: FWD / REV / STOP / RDST / RSTEF M1143 ASCII / RTU mode selection. ON : RTU mode, OFF: ASCII mode. Supported communication instructions:

RS / MODRD / MODWR / MODRW (When M1177 = ON, FWD / REV / STOP / RDST / RSTEF can also be applied. User sets and resets M1161 8/16-bit mode. ON: 8-bit mode. OFF: 16-bit mode Supported communication instructions: RS User sets M1177 Enable the communication instruction for Delta VFD series inverter. ON: VFD-A (Default), OFF: other models of VFD Supported communication instructions: FWD / REV / STOP / RDST / RSTEF Special Function register D1038 Delay time of data response when PLC is SLAVE in COM2, COM3 RS-485 communication, Range: 0~10,000. (Unit: 0.1ms). By using EASY PLC LINK in COM2, D1038 can be set to send next communication data with delay. (unit:

one scan cycle) D1050~D1055 Converted data for Modbus communication data processing. PLC automatically converts the ASCII data in D1070~D1085 into Hex data and stores the 16-bit Hex data into D1050~D1055 Supported communication instructions: MODRD / RDST