3. Instruction Set 3. PLC COM3 RS-485: Associated flags (Auxiliary relays) and special registers (Special D) for communication instructions RS / MODRW and FWD / REV / STOP / RDST / RSTEF when M1177 = ON. 3-233 Special Function register D1168 The specific end word to be detected for RS instruction to execute an interruption request (I150) on COM2 (RS-485). Supported communication instruction: RS D1256~D1295 For COM2 RS-485 MODRW instruction. D1256~D1295 store the sent data of MODRW instruction. When MODRW instruction sends out data, the data will be stored in D1256~D1295. Users can check the sent data in these registers. Supported communication instruction:
MODRW D1296~D1311 For COM2 RS-485 MODRW instruction. D1296~D1311 store the converted hex data from D1070 ~ D1085 (ASCII). PLC automatically converts the received ASCII data in D1070 ~ D1085 into hex data. Supported communication instruction: MODRW Flag Function Action M1136 COM3 retain communication settings. Communication settings will be reset (changed) according to the content in D1109 after every scan cycle. Users can set ON M1136 if the communication protocol requires to be retained.
When M1136 = ON, communication settings will not be reset (changed) when communication instructions are being processed, even if the content in D1109 is changed User sets and resets M1320 COM3 ASCII / RTU mode selection. ON : RTU mode, OFF: ASCII mode. M1316 COM3 sending request. Before executing communication instructions, users need to set M1316 to ON by trigger pulse, so that the data sending and receiving will be started. When the communication is completed, PLC will reset M1316 automatically. User sets, system resets M1317 Data receiving ready. When M1317 is ON, PLC is ready for data receiving. System sets M1318 COM3 data receiving completed. System sets, user resets