Delta DVP-ES2 — 3.8 Detailed Instruction Explanation

3. Instruction Set Points to note: 1. There is no limitation on the times of using this instruction. However, the register No. designated in S 3 ~ S 3 +19 cannot be repeated. 2. For 16-bit instruction, S 3 occupies 20 registers. In the program example above, the area designated in S 3 is D100 ~ D119. 3. Before the execution of PID instruction, users have to transmit the parameters to the designated register area by MOV instruction. If the designated registers are latched, use MOVP instruction to transmit all parameters only once 4. Settings of S 3 in the 16-bit instruction: 3-259 Device Function Setup Range Explanation No. S 3: Sampling time (T ) S 1~2,000 (unit:

10ms) Time interval between PID calculations and updates of MV. If T S = 0, PID instruction will not be enabled. If T is less than 1 program S scan time, PID instruction sets S 3 as 1 program scan time, i.e. the minimum T has to be longer than the program S scan time. S 3+1: Propotional gain (K ) P 0~30,000(%) The proportion for magnifying/minifying the error between SV and PV. S 3+2: Integral gain (K) I 0~30,000(%) The proportion for magnifying/minifying the integral value (The accumulated error). For control mode K0~K8. Integral time constant (T) I 0~30,000 (ms) For control mode K10 S 3+3:

Derivative gain (K ) D -30,000~30,000 (%) The proportion for magnifying/minifying the derivative value (The rate of change of the process error). For control mode K0~K8 Derivative time constant (T ) D -30,000~30,000 (ms) For control mode K10