Delta DVP-ES2 — 3.8 Detailed Instruction Explanation

DVP-ES2/EX2/SS2/SA2/SX2/SE&TP Operation Manual - Programming 3-260 Device Function Setup Range Explanation No. S 3+4: Control mode 0: Automatic control 1: Forward control (E = SV - PV). 2: Reverse control (E = PV - SV). 3: Auto-tuning of parameter exclusively for the temperature control. The device will automatically become K4 when the auto-tuning is completed and KP, KI and KD is set with appropriate value (not avaliable in the 32-bit instruction). 4: Exclusively for the adjusted temperature control (not avaliable in the 32-bit instruction). 5: Automatic mode with MV upper/lower bound control. When MV reaches upper/lower bound, the accumulation of integral value stops. 7: Manual control 1:

User set an MV. The accumulated integral value increases according to the error. It is suggested that the control mode should be used in a control environment which change more slowly. DVP-ES2/DVP-EX2/DVP-SS2/DVP-SA2/DVP-SX2 series PLCs whose version is 2.00 (or above), and DVP-SE series PLCs whose version is 1.00 (or above) are supported. 8: Manual control 2: User set an MV. The accumulated integral value will stop increasing. When the control mode becomes the automatic mode (the control mode K5 is used), the instruction PID outputs an appropriate accumulated integral value according to the last MV.

DVP-ES2/DVP-EX2/DVP-SS2/DVP-SA2/DVP-SX2 series PLCs whose version is 2.00 (or above), and DVP-SE series PLCs whose version is 1.00 (or above) are supported. 10: T / T mode: The control changes the integra gain and I D the differential gain into integral time constant and differential time constant. S 3+5: Tolerable range for error (E) 0~32,767 E = the error between SV and PV. If S 3 +5 is set as 5, when E is between -5 and 5, E will be 0. When S 3 +5 = K0, the function will not be enabled. S 3+6: Upper bound of output value (MV) -32,768~32,767 Ex: if S 3+6 is set as 1,000, MV will be 1,000 when it exceeds 1,000.

S 3+6 has to be bigger or equal to S 3+7, otherwise the upper bound and lower bound value will switch. S 3+7: Lower bound of output value (MV) -32,768~32,767 Ex: if S 3+7 is set as -1,000, MV will be -1,000 when it is smaller than -1,000.. S 3+8: Upper bound of integral value -32,768~32,767 Ex: if S 3+8 is set as 1,000, the integral value will be 1,000 when it is bigger than 1,000 and the integration will stop. S 3+8 has to be bigger or equal S 3 +9; otherwise the upper bound and lower bound value will switch